How to Size a Coolant Pump for Direct-to-Chip Cooling Systems

Sources:GuangDong Shenpeng Technology Co., Ltd.  Release date: 2026-11-27  Browsing:

Size a direct-to-chip (DTC) cooling pump on two numbers: the total flow demanded by all cold plates, and the total pressure drop of the loop, then add margin and pick the model. For a typical DTC rack that lands on a 24 V brushless DC pump such as the P4552 or P6092, or the 48 V P609248I04 for OCP and AI racks. Get either number wrong and the chips either overheat or the pump wastes energy. This guide gives the sizing steps, a worked example, and the models that fit.


02085f0ce13941888b2b99f3cbb29ce8_20261007134334_9675.jpg


Step 1: Sum the Cold-Plate Heat Load Into Total Flow

Direct-to-chip cooling removes heat from CPUs and GPUs through cold plates, so the pump must move enough coolant to carry that heat at your chosen ΔT:

Required flow = Total chip heat load ÷ (density × specific heat × ΔT)

As a planning figure, count the worst-case TDP of every chip on a cold plate and add overhead. A rack carrying eight high-power GPUs at roughly 120–150 kW total, with a 10 °C ΔT, needs on the order of 150–200 L/min rack-wide — but that is the loop total; divide it across the CDU loops feeding the rack to get the per-pump demand. Size from worst-case TDP, never the average.


Step 2: Build the Cold-Plate Pressure-Drop Budget

Head is where DTC loops hurt. Cold plates are the dominant restriction, and every other component adds on top:

 - Cold plates: high-performance plates add roughly 3–8 m each — count the worst single plate in a parallel arrangement.

 - Quick disconnects and manifolds: 1–3 m.

 - CDU internals: filter, heat exchanger, control valve — several meters.

 - Pipe runs and fittings: small but cumulative.

A DTC rack loop commonly totals 15–25 m of dynamic head before margin. Add 10–20% for fouling and filter loading.


Step 3: Add Margin and Pick the Pump

Worked example: a single-rack DTC loop requiring about 25 L/min at 18 m of head on a 24 V bus. The P4552 (11 L/min, 11 m) undershoots both numbers; the P6092 (24 V, 25 L/min, 27 m, 88 W) covers the duty with head to spare. On a 48 V OCP rack, the P609248I04 (48 V, 30 L/min, 20 m, 100 W) is the match. Rule: choose the smallest model whose curve covers both flow and head at the operating point.

ModelVoltageMax flowMax headRated power
P455224 V11 L/min11 m28 W
P609224 V25 L/min27 m88 W
P609248I0448 V30 L/min20 m100 W


Common Sizing Mistakes

 - Sizing on average TDP instead of worst-case.

 - Forgetting quick disconnects, filters, and the heat exchanger in the head budget.

 - Choosing by maximum flow and ignoring head — the farthest cold plate starves first.

 - Oversizing "for safety," which pushes the pump off its best-efficiency point and hurts PUE.


FAQ

Q: What two numbers size a direct-to-chip pump?

A: Total required flow (from total chip heat load and design ΔT) and total loop head (from every restriction, dominated by the cold plates).

Q: How much head does a DTC loop need?

A: Typically 15–25 m for a rack loop, once you sum the cold plates, quick disconnects, manifold, and CDU internals — plus 10–20% margin.

Q: Which pump is standard for a DTC rack CDU?

A: The P6092 (24 V, 25 L/min, 27 m, 88 W) for most 24 V DTC loops, and the P609248I04 (48 V, 30 L/min, 20 m, 100 W) for 48 V OCP/AI racks.

Q: Can one pump cool a whole AI rack?

A: One pump per CDU loop can, if its flow and head cover the combined cold-plate demand. For very dense racks, split the loop across two CDUs.

Q: How do I avoid overheating a GPU?

A: Size flow to worst-case TDP, budget head to the worst cold plate, and add margin. Undersized flow and head are the two direct causes of throttling.


Direct-to-Chip Cooling Pumps from Shenpeng Technology

Shenpeng Technology's brushless DC pumps are sized for direct-to-chip loops: the P4552 (24 V, 11 L/min, 11 m, 28 W), the P6092 (24 V, 25 L/min, 27 m, 88 W), and the P609248I04 (48 V, 30 L/min, 20 m, 100 W). Contact our engineering team with your cold-plate count, worst-case TDP, target ΔT, and loop layout — we will confirm the duty point and recommend the right cold plate pump.



TAG:

direct-to-chip cooling pump

Return
Contact

Address:No.30, Dapu lndustrial Street, Changping, Dongguan, Guangdong, China

Mob/Whatsapp:+8615322968598

+8613650475520

E-mail: sp005@dgshenpeng.com

Guangdong Shenpeng Technology Co., Ltd. designs and manufactures brushless DC water pumps for EV battery cooling, energy storage, data-center liquid cooling and home appliances — IATF 16949 and CNAS certified, 15 million units a year, OEM/ODM.

GuangDong Shenpeng Technology Co., Ltd. Copyright © 2018         FriendLink: mini pump  [SiteMap] Privacy Policy