Size a direct-to-chip (DTC) cooling pump on two numbers: the total flow demanded by all cold plates, and the total pressure drop of the loop, then add margin and pick the model. For a typical DTC rack that lands on a 24 V brushless DC pump such as the P4552 or P6092, or the 48 V P609248I04 for OCP and AI racks. Get either number wrong and the chips either overheat or the pump wastes energy. This guide gives the sizing steps, a worked example, and the models that fit.

Step 1: Sum the Cold-Plate Heat Load Into Total Flow
Direct-to-chip cooling removes heat from CPUs and GPUs through cold plates, so the pump must move enough coolant to carry that heat at your chosen ΔT:
Required flow = Total chip heat load ÷ (density × specific heat × ΔT)
As a planning figure, count the worst-case TDP of every chip on a cold plate and add overhead. A rack carrying eight high-power GPUs at roughly 120–150 kW total, with a 10 °C ΔT, needs on the order of 150–200 L/min rack-wide — but that is the loop total; divide it across the CDU loops feeding the rack to get the per-pump demand. Size from worst-case TDP, never the average.
Step 2: Build the Cold-Plate Pressure-Drop Budget
Head is where DTC loops hurt. Cold plates are the dominant restriction, and every other component adds on top:
- Cold plates: high-performance plates add roughly 3–8 m each — count the worst single plate in a parallel arrangement.
- Quick disconnects and manifolds: 1–3 m.
- CDU internals: filter, heat exchanger, control valve — several meters.
- Pipe runs and fittings: small but cumulative.
A DTC rack loop commonly totals 15–25 m of dynamic head before margin. Add 10–20% for fouling and filter loading.
Step 3: Add Margin and Pick the Pump
Worked example: a single-rack DTC loop requiring about 25 L/min at 18 m of head on a 24 V bus. The P4552 (11 L/min, 11 m) undershoots both numbers; the P6092 (24 V, 25 L/min, 27 m, 88 W) covers the duty with head to spare. On a 48 V OCP rack, the P609248I04 (48 V, 30 L/min, 20 m, 100 W) is the match. Rule: choose the smallest model whose curve covers both flow and head at the operating point.
| Model | Voltage | Max flow | Max head | Rated power |
| P4552 | 24 V | 11 L/min | 11 m | 28 W |
| P6092 | 24 V | 25 L/min | 27 m | 88 W |
| P609248I04 | 48 V | 30 L/min | 20 m | 100 W |
Common Sizing Mistakes
- Sizing on average TDP instead of worst-case.
- Forgetting quick disconnects, filters, and the heat exchanger in the head budget.
- Choosing by maximum flow and ignoring head — the farthest cold plate starves first.
- Oversizing "for safety," which pushes the pump off its best-efficiency point and hurts PUE.
FAQ
Q: What two numbers size a direct-to-chip pump?
A: Total required flow (from total chip heat load and design ΔT) and total loop head (from every restriction, dominated by the cold plates).
Q: How much head does a DTC loop need?
A: Typically 15–25 m for a rack loop, once you sum the cold plates, quick disconnects, manifold, and CDU internals — plus 10–20% margin.
Q: Which pump is standard for a DTC rack CDU?
A: The P6092 (24 V, 25 L/min, 27 m, 88 W) for most 24 V DTC loops, and the P609248I04 (48 V, 30 L/min, 20 m, 100 W) for 48 V OCP/AI racks.
Q: Can one pump cool a whole AI rack?
A: One pump per CDU loop can, if its flow and head cover the combined cold-plate demand. For very dense racks, split the loop across two CDUs.
Q: How do I avoid overheating a GPU?
A: Size flow to worst-case TDP, budget head to the worst cold plate, and add margin. Undersized flow and head are the two direct causes of throttling.
Direct-to-Chip Cooling Pumps from Shenpeng Technology
Shenpeng Technology's brushless DC pumps are sized for direct-to-chip loops: the P4552 (24 V, 11 L/min, 11 m, 28 W), the P6092 (24 V, 25 L/min, 27 m, 88 W), and the P609248I04 (48 V, 30 L/min, 20 m, 100 W). Contact our engineering team with your cold-plate count, worst-case TDP, target ΔT, and loop layout — we will confirm the duty point and recommend the right cold plate pump.
Address:No.30, Dapu lndustrial Street, Changping, Dongguan, Guangdong, China
Mob/Whatsapp:+8615322968598
+8613650475520
Guangdong Shenpeng Technology Co., Ltd. designs and manufactures brushless DC water pumps for EV battery cooling, energy storage, data-center liquid cooling and home appliances — IATF 16949 and CNAS certified, 15 million units a year, OEM/ODM.